TBC TAR-263M Automatic Recloser RCCB

TAR-263M
TBC TAR-263M Automatic Recloser RCCB
TBC TAR-263M Automatic Recloser RCCB

The TAR-263M is an advanced Automatic Recloser RCCB engineered to automatically restore power supply after nuisance tripping caused by temporary earth leakage faults. Combining intelligent reclosing technology with reliable residual current protection, this device significantly improves supply continuity in residential, commercial, and infrastructure applications while maintaining the highest standards of electrical safety.

Key Features

  • Automatic reclosing after RCCB trip for enhanced supply continuity
  • Up to 6 automatic reclose attempts with intelligent delay sequence
  • Progressive delay timing: 10s / 20s / 30s / 60s / 120s / 600s
  • Manual lock-out protection after 6 failed reclosing attempts
  • Auxiliary contacts (1 NO + 1 NC) for remote control and monitoring
  • DIN-rail mounting for easy installation in standard enclosures
  • Electromechanical trip unit for high reliability and durability
  • 63A rated current with 100mA residual current sensitivity
  • Fast tripping time: 0.4s to 1.0s
  • Padlockable design for enhanced safety and security
  • Wide operating temperature range: -35°C to +70°C
  • SIRIM approved and IEC 61008-1 compliant

The TAR-263M Automatic Recloser RCCB represents a significant advancement in electrical protection technology, addressing one of the most common challenges in modern electrical installations: nuisance tripping due to temporary earth leakage faults. This intelligent device combines traditional RCCB protection with an automatic reclosing mechanism that attempts to restore power supply after a trip event.

When an earth leakage fault occurs, the RCCB trips to protect against electric shock hazards. The integrated recloser then automatically attempts to restore power after a predetermined delay. If the fault was temporary (such as moisture, transient surges, or environmental conditions), power is successfully restored without manual intervention. The device employs an intelligent progressive delay sequence across 6 attempts, allowing sufficient time for temporary faults to clear.

After 6 unsuccessful reclosing attempts, the system locks out and requires manual reset, ensuring that persistent faults are not repeatedly energized. This smart logic provides the optimal balance between supply continuity and electrical safety, making it ideal for critical applications where power interruption must be minimized.

The device features auxiliary contacts for integration with building management systems, remote monitoring, and alarm circuits, enabling proactive maintenance and fault diagnosis in modern smart installations.

Recloser Mechanism: The TAR-263M incorporates a sophisticated automatic reclosing mechanism rated for 220/240V AC at 50Hz, with a power consumption of 30VA. The recloser activates within 0.4 to 1.0 seconds after an RCCB trip and executes up to 6 automatic reclose attempts with progressively increasing delays (10s, 20s, 30s, 60s, 120s, and 600s). This intelligent delay sequence allows temporary faults to clear while preventing rapid cycling on persistent faults.

RCCB Protection: The residual current protection is rated at 63A with a 100mA sensitivity (I∆n), suitable for fire protection and equipment safety applications. The 1P+N configuration provides protection for single-phase circuits. With a rated breaking capacity of 500A and conditional short-circuit current rating of 6kA, the device offers robust protection even under fault conditions.

Auxiliary Contacts: Equipped with 1 NO + 1 NC dry contacts rated for 250V / 2A, enabling remote status indication, alarm signaling, and integration with SCADA or building management systems.

Construction: Features an electromechanical trip unit for superior reliability and immunity to electronic interference. The device is designed for 35mm DIN rail mounting with IP20 protection degree, suitable for installation in standard distribution boards and enclosures.

Durability: Rated for 5,000 electrical cycles, ensuring long service life in demanding applications. The padlockable design allows for secure lockout/tagout procedures during maintenance.

Environmental Performance: Operates reliably across an extended temperature range of -35°C to +70°C with humidity tolerance up to 93%, making it suitable for harsh environmental conditions including outdoor installations and tropical climates.

  • Residential distribution boards for enhanced home power continuity
  • Commercial buildings and office complexes to minimize business interruption
  • Water heater circuits prone to moisture-related nuisance tripping
  • Outdoor electrical installations exposed to environmental conditions
  • Unstable power environments with frequent transient disturbances
  • Telecommunications equipment rooms and data centers
  • Infrastructure panels for utilities and public services
  • Remote installations where manual reset is impractical
  • Agricultural facilities and farm installations
  • Industrial auxiliary circuits requiring high availability
  • Street lighting and outdoor illumination systems
  • Refrigeration and cold storage facilities
  • Pump stations and water treatment plants
  • Building management systems with remote monitoring requirements
Recloser (REC) Mechanism
Rated Voltage (Un)220 / 240 V AC
Rated Frequency50 Hz
Power Consumption30 VA
Tripping Time0.4 s to 1.0 s
Reclose Attempts6 times
Reclosing Delay Sequence10s / 20s / 30s / 60s / 120s / 600s
RCCB Parameters
Rated Current (In)63 A
Rated Residual Current (I∆n)100 mA
Number of Poles1P + N
Rated Breaking Capacity (Im)500 A (at In = 40A)
Rated Conditional Short-Circuit Current (Inc)6 kA
Rated Residual Short-Circuit Capacity (I∆c)6 kA
Non-Trip Current (I∆no)0.5 I∆n
Auxiliary Contacts
Contact Type1 NO + 1 NC (Dry Contact)
Maximum Voltage250 V
Maximum Current2 A
Mechanical & Installation
Mounting TypeDIN Rail (35 mm)
Trip Unit TypeElectromechanical
Electrical Endurance5,000 cycles
PadlockableYes
Degree of ProtectionIP20
Dimensions
Height82 mm
Width92 mm
Depth76 mm
Environmental Conditions
Operating Temperature-35 °C to +70 °C
Relative Humidity0 to 93%
Protection DegreeIP20
Standards & Compliance
CertificationsSIRIM Approved
Standards ComplianceIEC 61008-1